Welcome, Neighbors of
Montbello
Furnace Repair in Montbello, CO
Montbello went up quickly as one neighborhood in far northeast Denver, block after block of similar homes with similar furnaces installed at similar times. When one starts failing to stay lit, the street often follows. Family owned and five star rated since 2009.
5-star rated · Local & Family-owned since 2009
Licensed & Insured
Family Owned
NATE Certified
EPA Certified
BBB Accredited
Serving Denver Metro
See your neighbor deals
MoJo Home Services
Furnace Repair
Furnace Repair in Montbello, Denver
Montbello sits at 5,305 feet in far-northeast Denver, 26 feet above the city's official 5,279. That elevation carries a 13.2% gas furnace derate under the NFPA 54 convention: a nameplate 100,000 BTU/hr furnace produces about 86,800 BTU/hr, and an 80% AFUE model delivers roughly 69,400 BTU/hr into the ducts. The single most common no-heat call from this neighborhood is a furnace that lights normally and shuts down four to seven seconds later, and that is a flame sensing failure - a measurable one, in microamps.
Why does my Montbello furnace light and then shut down seconds later?
Because the control board lit the burners, waited for proof that flame existed, did not get enough proof, and closed the gas valve as designed. That timing is the signature: ignition works, so the igniter and gas delivery are functional, and the failure lands in the flame proving circuit. Three or four repeats and the board locks out. In Montbello this pattern accounts for more mid-winter calls than any other single fault, and it is almost never the control board that needs replacing.
How does a flame sensor actually work?
Through flame rectification. The board applies alternating voltage to a single rod sitting in the flame, and the flame itself behaves as a diode - conducting far better in one direction than the other because the burner assembly presents a much larger grounded surface than the rod does. The board reads the resulting direct current in microamps. That is why a flame sensor cannot be tested with a continuity check and why the ground path matters as much as the rod: a rusted burner tray or a loose burner ground can kill the signal on a furnace whose sensor is perfectly clean.
What flame signal should a Montbello furnace read?
Typically 2 to 6 microamps on a healthy system, measured in series with the sensor lead while the burners run. Most control boards drop out somewhere between 0.5 and 1.0 microamps. A furnace reading 1.2 microamps is not "fine" - it is a call waiting to happen on the next cold night, because the signal falls as the rod accumulates oxide. Any Montbello technician who replaces a flame sensor without recording the signal before and after has no evidence the repair did anything.
Why does 13.2% make flame sensing worse here?
Because the derate only holds if the furnace was converted for 5,305 feet. If it was not, the burner runs rich, and a rich flame deposits a silicon and oxide film on the sensor rod much faster than a correctly set flame does. The homeowner then gets a cleaning that works for six weeks, then another. The film is the symptom; the fuel rate is the cause. Verifying manifold pressure and orifice sizing against Montbello's elevation is what turns a repeating flame sensor complaint into a fixed furnace.
Is cleaning the sensor the right repair?
It is the right first step, done correctly - a light abrasive that removes the film without cutting grooves into the rod, since a scored rod builds film faster afterwards. But if the signal will not come back above roughly 2 microamps after cleaning, the rod is spent or the ground path is compromised, and that is a replacement rather than another cleaning. If the signal is strong and the furnace still drops out, the fault has moved to the board's flame circuit or the wiring, and we test there instead of guessing.
Does being a Denver neighborhood change permitting?
Yes, in a way that matters. Montbello is inside the City and County of Denver, so gas appliance permits go through Denver's consolidated authority rather than a separate county office - different from the Adams and Arapahoe jurisdictions immediately around it. Flame sensors, igniters, inducers and pressure switches generally are not permitted work. A furnace changeout is, and we file it.
Where else in far-northeast Denver do you work?
Across the whole northeast quadrant and past the city line. Green Valley Ranch sits 26 feet lower at 13.1% and Central Park 16 feet lower, both effectively Montbello's numbers, while Commerce City is 148 feet down at 12.6% and in a different county for permitting. Call 720-807-4050 for furnace diagnosis anywhere in that area.
Other Montbello-area pages
If you are comparing notes with someone a town over, we cover furnace repair in Green Valley Ranch, furnace repair in Central Park, furnace repair in Commerce City too.
If it is the other system acting up instead, start at AC repair in Montbello.
See furnace repair for the service itself, or everything in Montbello for everything we do there.

Montbello
Home Of The $39 Diagnosis
Book your diagnostic today!
The $39 diagnostic service is a professional troubleshooting visit performed by a certified MoJo technician to identify the root cause of an HVAC issue.
Frequently Asked Questions
Why does my furnace in Montbello start and then quit after a few seconds?
That timing points at flame sensing. The burners light, the control board fails to read enough flame current, and it closes the gas valve within about four to seven seconds. Healthy flame signal is roughly 2 to 6 microamps; most boards drop out below 1. In Montbello the underlying cause is often a rich flame from a furnace never converted for 5,305 feet, which coats the sensor rod quickly.
What is the gas furnace derate in Montbello?
13.2%, from 5,305 feet under the 4% per 1,000 feet convention above 2,000 feet. A 100,000 BTU/hr furnace here supplies about 86,800 BTU/hr of input, with roughly 69,400 BTU/hr reaching the ducts at 80% AFUE. Montbello sits 26 feet above Denver's official 5,279-foot elevation, so its derate is a tenth of a point wider than the citywide figure.
Can I clean a flame sensor myself?
You can, with the power off and a light abrasive that lifts the film without scoring the rod - a scored rod fouls faster afterwards. What a homeowner cannot do is measure the result. If a Montbello furnace needs cleaning every few weeks, the flame itself is wrong, usually because the furnace still fires at sea-level rates instead of the 13.2% derated rate for 5,305 feet.
Should the control board be replaced if the furnace keeps dropping out?
Rarely, and almost never first. In Montbello the flame proving circuit fails far more often at the rod, the ground path or the burner tray than at the board. A technician should record the flame signal in microamps before and after cleaning, confirm burner ground, and only then test the board's flame circuit. Boards are among the most frequently replaced parts that were never actually broken.
Who issues furnace permits for a Montbello home?
Denver does. Montbello is within the City and County of Denver, so gas appliance permitting runs through Denver's consolidated authority rather than through Adams or Arapahoe County, even though both border the neighborhood. Component repairs such as a flame sensor, igniter or inducer motor generally need no permit. A furnace replacement does, and we file it as part of the job.
MoJo Home Services
A note for our neighbors
Montbello looks after its own, and we have felt that from our very first call here. Families pass our name across the street and down the block, and that is how nearly all of our furnace repair work arrives. Being trusted by a neighborhood like this one means more than we let on.

Furnace Repair
In
Montbello
Share Your Experience
Thank you for supporting our local family business. If we did right by you, we'd love to hear about it on any site you use.
- Write a Google reviewQuick & easy
- Find us on YelpRead what neighbors said
- Review us on FacebookShare with friends
- Recommend us on NextdoorTell your neighbors
Your referrals and reviews not only mean so much to us, they also help the community know who to trust to Get their Home's MoJo Back!
Honest feedback is what we're after, good or bad. If something fell short, call us at the office first and we'll make it right.